+86-312-6775656
HZGC-1210 Online sistem za nadgledanje analize rastvorenog gasa (DGA) za energetski transformator

HZGC-1210 Online sistem za nadgledanje analize rastvorenog gasa (DGA) za energetski transformator

On-online sistem praćenja hromatograma transformatorskog ulja tipa HZGC-1210 može realizovati sljedeće funkcije: automatsko čišćenje cirkulacije, odvajanje ulja, ulja i plina, analizu uzoraka, obradu podataka i alarm u realnom vremenu; Mogao bi brzo online pratiti sadržaj i rast kvarnog plina...
Product Details ofHZGC-1210 Online sistem za nadgledanje analize rastvorenog gasa (DGA) za energetski transformator

 

On-online sistem praćenja hromatograma transformatorskog ulja tipa HZGC-1210 može realizovati sljedeće funkcije: automatsko čišćenje cirkulacije, ulje u, odvajanje ulja i plina, analiza uzoraka, obrada podataka i stvarna{{3} }vremenski alarm; Mogao bi brzo online pratiti sadržaj i rast kvarnog plina otopljenog u ulju-uronjenih energetskih HV transformatora opreme kao što su transformatori. Kroz ekspertni sistem za dijagnostiku kvarova, mogao bi ranije predvidjeti skriveni problem kvara opreme, izbjegavajući nesreće opreme, kako bi se smanjili veliki gubici i poboljšala pouzdanost rada opreme. Kao nova generacija proizvoda u oblasti uljnog hromatograma on-monitoringa, sistem će pružiti stabilna i pouzdana rješenja za energetski transformator za realizaciju on-line daljinske DGA analize. Dakle, to je snažna garancija za sprovođenje državnog remonta elektroenergetskog sistema.

online dga system_

Sistem HZGC-1210 je dizajniran na osnovu svih prednosti on-line praćenja uljnog hromatograma u zemlji i inostranstvu. Dakle, sistem ima očigledne prednosti u aspektima stabilnosti, pouzdanosti i tačnosti.

♦ On-line testing the concentration and growth rate of H2,CO,CO2,CH4,C2H4,C2H2,C2H6

♦ The method of quantitative cleaning and circulatory sampling could truly reflect the state of gas dissolved in oil.

♦ Oil-gas separation is safe and reliable without any pollution. The users could choose to discharge the transformer oil or not.

♦ It adopted dedicated composite chromatographic column to improve the degree of separation of gas component.

♦ It adopted imported detector to enhance the sensitivity of testing hydrocarbon gases.

♦ The gas detection technique has high stability and precision with ± 10 percent error range.

♦ Mature and reliable as the communication mode is, it adopted standard networking protocols and could support remote data transmission.

♦ Data collection, adopted the oversampling technology Δ - ∑ analog-digital converter with 24-bit resolution and automatic calibration, is highly reliable.

♦ Diverse data display and inquiry modes could provide report and trend chart. The storage life of historical data is 10 years.

♦ It has strong environmental adaptability, widely used in cold, hot, high humidity and high altitude areas.

♦ The performance of anti-interference is outstanding. The electromagnetic compatibility could meet GB/T17626 and IEC61000 standard.

♦ It offered 2 level of alarming set. Alerting signal could spread widely.

♦ Open database could access to LAN of electric system.

Osim toga, HZGC-1210 sistem koristi modularni dizajn sa primjenom ugrađenih procesora visokih performansi, čineći hromatografski sistem za praćenje na mreži stabilnijim i pouzdanijim. Ima sljedeće karakteristike:

♦ It has faster analysis cycle which can be set by users themselves. The minimum monitoring cycle is 40 to 60 minutes. We recommend setting 24 hours as an inspection cycle;

♦ It takes only 10 minutes to separate oil and gas. It uses special environmental adaptation technology to eliminate any change of gas distribution coefficient caused by the temperature and humidity changes.

♦Analyzed oil sample adopted the technique of degassing and buffering, removing the mingled bubble in oil sample of reinjection transformer. The technique of multilayer isolated reinjection oiling (return oiling) could guarantee the carried gas would not be taken into the transformer.

♦ The minimum limit of detection of C2H2 can reach 0.1-0.5 μ L/L.

♦ It adopted double circuit and multi{{0}}mode thermostatic control with ± 0.1 degree temperature control accuracy. The device is equipped with industrial air conditioning which has the function of automatic constant temperature control.

♦ The embedded processor control system is multi-function, combining oil-gas separation, data acquisition, chromatographic analysis, concentration calculation, data alarming, and equipment condition monitoring. Cases like data loss would be avoided, greatly improving the reliability and stability of the system.

♦ Functional interface circuit adopted opto-isolator to further improve the ability of anti-interference.

♦ Via Ethernet, it could realize full-digital and remote data transmission, parameter setting and control.

♦ It improves the function of fault diagnosis, applying modified three ratio method, David trigonometry and cube graphic method to draw the diagnosis result;

♦ It strengthens self-inspection and adds the function of remote maintenance and alarming for equipment abnormality

♦ It supports 61850 communication protocol, providing networking for monitoring equipment of the same kind, so that it can realize concentrated remote diagnosis in a certain area.

♦ The system adopted 19 standard case and high-integrated modular design, which is easy to install and maintain with user-friendly operation.

♦ With wide expandability, it could integrate with other monitoring device conveniently.

♦ The design of non-cylinder saves the time and money to change the carrier gas every year so that after sale maintenance would be much easier. Without high pressure vessel nearby, transformers would be safer, free from any potential risk.

br.

Naziv parametra

vrijednost

1

Model

HZGC-1210

2

Radna temperatura

-40 degree -+70 degree

3

Radna vlažnost

Relative humidity5-95 percent (interior of device shall be free from condensation and ice.)

4

Atmosferski pritisak

70kPa-110kPa

5

Napajanje

AC 220 V±10 percent , 50Hz

6

Praćenje sadržaja

Pratiti H2, CO, CO2, CH4, C2H4, C2H2, C2H6 u aspektima ukupnog ugljovodonika, relativne stope rasta i apsolutne vrijednosti rasta. (opciono za odabir ulja s malo vode)

7

Analiza i dijagnoza

Conduct analysis and diagnosis for the monitoring data via improved three-ratio method, Duval's triangle and cubic graphic method. Provide the original chromatography.

8

Minimalni period detekcije

Range between 40 and 60min, up to user's settings. default 24 hours

9

Metoda uzorkovanja

Cirkulatorno uzorkovanje bi precizno odražavalo status vazduha u transformatorima.

10

Metoda odvajanja nafte{0}}a

metoda vakuumskog degaziranja

11

Vek skladištenja podataka

Više od ili jednako 10 godina

12

Opremljen transportnim plinom

gas generator

13

Prati gas

Opseg mjerenja

Najniža vrijednost detekcije

Greška mjerenja

1)

H2

1 - 10000 µ l/l

1µ l/l

±10 percent

2)

CO, CO2

5-  50000 µ l/l

5µ l/l

±10 percent

3)

CH4

0.1 - 20000 µ l/l

0.1-0.5 µ l/l

±10 percent

4)

C2H4

0.1 - 20000µ l/l

0.1-0.5 µ l/l

±10 percent

5)

C2H6

0.1 - 20000 µ l/l

0.1 -0.5µ l/l

±10 percent

6)

C2H2

0.1 - 5000 µ l/l

0.1-0.5 µ l/l

±10 percent

7)

H2O(optional)

1 - 800 µ l/l

1µ l/l

±10 percent

8)

Ukupni ugljikovodici

1 - 8000 µ l/l

9)

Ukupan sadržaj vazduha

0.2 - 15 posto

14

Stability(measured deviation)

Under the same test condition, the deviation of test result shall be no more than 10 percent (medium concentration)

15

Otpornost na elektrostatičko pražnjenje

Grade 4,± 8kV-± 15kV

16

Električni brzi prolazni imunitet

Grade 4,± 4kV

17

Imunitet na udar (šok).

Grade 4,± 4kV

18

Sposobnost otpornosti na zemljotres: seizmički val je sinusni val. Vrijeme trajanja: trokružni talas. Faktor sigurnosti: 1,67

Područje sa stepenom 9 seizmičkog intenziteta:

Horizontalno ubrzanje tla {{0}}.4g, vertikalno ubrzanje tla 0.2g

Područje sa stepenom 8 seizmičkog intenziteta:

Ground horizontal acceleration {{0}}.25g,  ground vertical acceleration 0.125g

Područje sa stepenom 7 seizmičkog intenziteta:

Horizontalno ubrzanje tla {{0}}.2g, vertikalno ubrzanje tla 0.1g

19

Temperatura skladištenja i transporta u ekstremnim uslovima

-40 degree -+ 80 degree

20

Zaštitno svojstvo ograde

Outdoor installation parts (the system and communication control unit) IP56

21

Granična dimenzija

širina 585mm dubina425mm visina 1010mm

22

Ukupna tezina

125 kg

23

Osnovna veličina

širina 700mm dubina 380mm visina300mm

image012

image014

image016

Popularni tagovi: HZGC-1210 Online sistem za nadgledanje analize rastvorenog gasa (DGA) za energetski transformator, Kina, dobavljači, proizvođači, cena, prodaja, test analize rastvorenog gasa transformatorskog ulja, onlajn dga (analiza rastvorenog gasa) praćenje, onlajn sistem za praćenje gasnog hromatografa, HZGC-1210, On line plinska hromatografija, online transformator za praćenje otopljenog plina